• PCE-PA 8300-1 Three-Phase Power Analyzer

PCE-PA 8300 3-Phase Power Meter / 3-Phase Power Analyzer
3-phase / 3 current clamps / LCD graphic display / SD card memory

The PCE-PA 8300 is a 3-Phase Power Meter / 3-Phase Power Analyzer that features a durable enclosure, SD card memory, a LCD graphic display, as well as apparent, effective, and reactive power measurement. The easy-to-use PCE-PA 8300 3-Phase Power Meter is the ideal tool for performing power and harmonics analysis as well as for measuring network capacity.

Set 1: Includes 3 current clamps for measurements up to 1200 A AC


- Voltage measurement range of 10 V ... 600 V AC
- Current measurement range of 20 A ... 1200 A AC (Set 1)
- Performance measurement range of 0 kW ... 9.999 MW (VA/VAR)
- Simultaneous display of harmonics and waveform
- Graphic Phasor diagram
- Captures transients including dip, swell, and outage
- SD card memory
- LCD graphic display
- Durable enclosure
- Compatibility with various manufacturers' power clamps
- Adjustable back-up interval, allowing for long-term data collection
- Auto-setting of measurement range (AC V)
- Power efficiency, delay angle, and frequency measurement
- Apparent, effective, and reactive power measurement
- Harmonic spectrum measurement up to the 50th order

Electrical specifications
Voltage Measurement (AC V)
Measurement RangeResolutionAccuracy
10 V ... 600 V (phase to neutral)0.1 V±(0.5 % + 0.5 V)
10 V ... 600 V (phase to phase0.1 V±(0.5 % + 0.5 V)
Current Measurement (AC A) Set 1
Measurement RangeResolutionAccuracy
20 A0.001 A (< 10 A)
0.01 A (≥ 10 A)
± (0.5 % + 0.1 A)
200 A0.01 A (< 100 A)
0.1 A (≥ 100 A)
± (0.5 % + 0.5 A)
1200 A0.1 A (< 1000 A)
1 A (≥ 1000 A)
± (0.5 A + 5 A)

Effective power
Measurement rangeResolutionAccuracy
0 KW ... 9.999 KW0.001 KW±(1 % + 0.008 KW)
10 KW ... 99.99 KW0.01 KW±(1 % + 0.08 KW)
100 KW ... 999.9 KW0.1 KW±(1 % + 0.8 KW)
1 MW ... 9.999 MW0.001 MW±(1 % + 0.008 MW)
Apparent Power
Measurement rangeResolutionAccuracy
0 KVA ... 9.999 KVA0.001 KVA±(1 % + 0.008 KVA)
10 KVA ... 99.99 KVA0.01 KVA±(1 % + 0.08 KVA)
100 KVA ... 999.9 KVA0.1 KVA±(1 % + 0.8 KVA)
1 MVA ... 9.999 MVA0.001 MVA±(1 % + 0.008 MVA)
Reactive Power
Measurement rangeResolutionAccuracy
0 KVAR ... 9.999 KVAR0.001 KVAR±(1 % + 0.008 KVAR)
10 KVAR ... 99.99 KVAR0.01 KVAR±(1 % + 0.08 KVAR)
100 KVAR ... 999.9 KVAR0.1 KVAR±(1 % + 0.8 KVAR)
1 MVAR ... 9.999 MVAR0.001 MVAR±(1 % + 0.008 MVAR)
Active Energy
Measurement rangeResolutionAccuracy
0 KWH ... 9.999 KWH0.001 KWh±(2 % + 0.008 KWh)
10.00 KWH ... 99.99 KWH0.01 KWh±(2 % + 0.08 KWh)
100.0 KWH ... 999.9 KWH0.01 KWh±(2 % + 0.8 KWh)
1 MWH ... 9.999 MWH0.001 MMh±(2 % + 0.008 MWh)
Apparent Energy
Measurement rangeResolutionAccuracy
0 KVARH ... 9.999 KVARH0.001 KVARh± (2 % + 0.008 KVARh)
10.00 KVARH ... 99.99 KVARH0.01 KVARh± (2 % + 0.08 KVARh)
100.0 KVARH ... 999.9 KVARH0.01 KVARh± (2 % + 0.8 KVARh)
1 MVARH ... 9.999 MVARH0.001 MVARh± (2 % + 0.008 MVARh)
Power Factor
Measurement rangeResolutionAccuracy
0 ... 10.01± 0.04
Delay Angle
Measurement rangeResolutionAccuracy
-180° ... +180°0.1°±1°
Frequency
Measurement rangeResolutionAccuracy
45 Hz ... 65 Hz0.1 Hz± 0.1 Hz
Harmonic of AC Voltage at 50 / 60 Hz
Measurement rangeResolutionAccuracy
1 ... 20th order0.001 ... 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 ... 30th order0.001 ... 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 ... 50th order0.001 ... 1 A
0.1 %
not specified
General specifications
Display3.7 in / 94.0 mm point-matrix LCD (320 * 240 pixel) with LED background lights
Safety standardsIEC1010CAT III 600V
Input resistance AC V10 MOhm
Operating frequency of current clamp40 Hz ... 1 kHz
Tested operating frequency of current clamp45 Hz ... 65 Hz
Overload protectionAC V
AC A
720 V RMS
1300 A with current clamp
Data StorageSD memory card
Refresh interval1 second
Data logging functionlogging with real-time speed on SD memory card
Record interval2 ... 7200 seconds
Data output (only for live display on computer)per USB or RS232, depending on connection cable
Operating temperature0° C ... +50° C / 32° F ... 122° F
Surrounding humidity< 80 % RH
8 x 1.5 V AA batteries
Voltage Supply9 V adapter
Current DrainMeasurement Device: 300 mA DC
current clamp: 34 mA DC
Maximum Wire Diameter50 mm / 1.9 in
WeightMeasurement Device: 948 g / 33.4 oz (incl. battery)
Current clamp: 467 g / 16.4 oz (incl. cable)
DimensionsDevice: 225 mm x 125 mm x 64 mm / 8.8 in x 4.9 in x 2.5 in
Current clamp: 210 mm x 64 mm x 33 mm / 8.2 in x 2.5 in x 1.2 in
Clamp jaw: 86 mm / 3.3 in (exterior)


1 x PCE-PA 8300 3-Phase Power Meter / 3-Phase Power Analyzer
3 x Current clamps (Set 1)
4 x Insulated alligator clips
4 x Safety test lines
6 x 1.5 V AA batteries
1 x 9 V mains adapter
1 x SD memory card
1 x Carrying case
1 x User manual

Write a review

Note: HTML is not translated!
    Bad           Good

PCE-PA 8300-1 Three-Phase Power Analyzer

  • Brand: PCE INSTRUMENTS
  • Product Code: PCE-PA 8300-1 Three-Phase Power Analyzer
  • Availability: Pre-Order
  • Rp.0.00

  • Ex Tax: Rp.0.00

Tags: JUAL PCE-PA 8300-1 Three-Phase Power Analyzer