Notice: Undefined index: message in /home/u7567509/public_html/system/storage/modification/catalog/controller/product/product.php on line 395 JUAL PCE-PA 8300-2 Three-Phase Power Analyzer
  • PCE-PA 8300-2 Three-Phase Power Analyzer

PCE-PA 8300 3-Phase Power Meter / 3-Phase Power Analyzer
3-phase / 3 current clamps / LCD graphic display / SD card memory

The PCE-PA 8300 is a 3-Phase Power Meter / 3-Phase Power Analyzer that features a durable enclosure, SD card memory, a LCD graphic display, as well as apparent, effective, and reactive power measurement. The easy-to-use PCE-PA 8300 3-Phase Power Meter is the ideal tool for performing power and harmonics analysis as well as for measuring network capacity.

Set 2: Includes 3 flexible Rogowski coils for measurements up to 3000 A AC


- Voltage measurement range of 10 V ... 600 V AC
- Current measurement range of 30 A ... 3000 A AC (Set 2)
- Performance measurement range of 0 kW ... 9.999 MW (VA/VAR)
- Simultaneous display of harmonics and waveform
- Graphic Phasor diagram
- Captures transients including dip, swell, and outage
- SD card memory
- LCD graphic display
- Durable enclosure
- Compatibility with various manufacturers' power clamps
- Adjustable back-up interval, allowing for long-term data collection
- Auto-setting of measurement range (AC V)
- Power efficiency, delay angle, and frequency measurement
- Apparent, effective, and reactive power measurement
- Harmonic spectrum measurement up to the 50th order


Electrical specifications
Voltage Measurement (AC V)
Measurement RangeResolutionAccuracy
10 V ... 600 V (phase to neutral)0.1 V±(0.5 % + 0.5 V)
10 V ... 600 V (phase to phase0.1 V±(0.5 % + 0.5 V)

Current measurement (AC A) Set 2
Measurement rangeResolutionAccuracy
30 A0.001 A (< 10 A)
0.01 A (≥ 10 A)
±(0.5 % + 0.1 A)
300 A0.01 A (< 10 A)
0.1 A (≥ 10 A)
±(0.5 % + 0.5 A)
3000 A0.1 A (< 1000 A)
1 A (≥ 1000 A)
±(0.5 A + 5 A)
Effective power
Measurement rangeResolutionAccuracy
0 KW ... 9.999 KW0.001 KW±(1 % + 0.008 KW)
10 KW ... 99.99 KW0.01 KW±(1 % + 0.08 KW)
100 KW ... 999.9 KW0.1 KW±(1 % + 0.8 KW)
1 MW ... 9.999 MW0.001 MW±(1 % + 0.008 MW)
Apparent Power
Measurement rangeResolutionAccuracy
0 KVA ... 9.999 KVA0.001 KVA±(1 % + 0.008 KVA)
10 KVA ... 99.99 KVA0.01 KVA±(1 % + 0.08 KVA)
100 KVA ... 999.9 KVA0.1 KVA±(1 % + 0.8 KVA)
1 MVA ... 9.999 MVA0.001 MVA±(1 % + 0.008 MVA)
Reactive Power
Measurement rangeResolutionAccuracy
0 KVAR ... 9.999 KVAR0.001 KVAR±(1 % + 0.008 KVAR)
10 KVAR ... 99.99 KVAR0.01 KVAR±(1 % + 0.08 KVAR)
100 KVAR ... 999.9 KVAR0.1 KVAR±(1 % + 0.8 KVAR)
1 MVAR ... 9.999 MVAR0.001 MVAR±(1 % + 0.008 MVAR)
Active Energy
Measurement rangeResolutionAccuracy
0 KWH ... 9.999 KWH0.001 KWh±(2 % + 0.008 KWh)
10.00 KWH ... 99.99 KWH0.01 KWh±(2 % + 0.08 KWh)
100.0 KWH ... 999.9 KWH0.01 KWh±(2 % + 0.8 KWh)
1 MWH ... 9.999 MWH0.001 MMh±(2 % + 0.008 MWh)
Apparent Energy
Measurement rangeResolutionAccuracy
0 KVARH ... 9.999 KVARH0.001 KVARh± (2 % + 0.008 KVARh)
10.00 KVARH ... 99.99 KVARH0.01 KVARh± (2 % + 0.08 KVARh)
100.0 KVARH ... 999.9 KVARH0.01 KVARh± (2 % + 0.8 KVARh)
1 MVARH ... 9.999 MVARH0.001 MVARh± (2 % + 0.008 MVARh)
Power Factor
Measurement rangeResolutionAccuracy
0 ... 10.01± 0.04
Delay Angle
Measurement rangeResolutionAccuracy
-180° ... +180°0.1°±1°
Frequency
Measurement rangeResolutionAccuracy
45 Hz ... 65 Hz0.1 Hz± 0.1 Hz
Harmonic of AC Voltage at 50 / 60 Hz
Measurement rangeResolutionAccuracy
1 ... 20th order0.001 ... 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 ... 30th order0.001 ... 1 A
0.1 %
± (2 % + 0.5 A)
± (2 % + 10 Digit)
21 ... 50th order0.001 ... 1 A
0.1 %
not specified
General specifications
Display3.7 in / 94.0 mm point-matrix LCD (320 * 240 pixel) with LED background lights
Safety standardsIEC1010CAT III 600V
Input resistance AC V10 MOhm
Operating frequency of current clamp40 Hz ... 1 kHz
Tested operating frequency of current clamp45 Hz ... 65 Hz
Overload protectionAC V
AC A
720 V RMS
1300 A with current clamp
Data StorageSD memory card
Refresh interval1 second
Data logging functionlogging with real-time speed on SD memory card
Record interval2 ... 7200 seconds
Data output (only for live display on computer)per USB or RS232, depending on connection cable
Operating temperature0° C ... +50° C / 32° F ... 122° F
Surrounding humidity< 80 % RH
8 x 1.5 V AA batteries
Voltage Supply9 V adapter
Current DrainMeasurement Device: 300 mA DC
current clamp: 34 mA DC
Maximum Wire Diameter50 mm / 1.9 in
WeightMeasurement Device: 948 g / 33.4 oz (incl. battery)
Current clamp: 467 g / 16.4 oz (incl. cable)
Dimensions

Device: 225 mm x 125 mm x 64 mm / 8.8 in x 4.9 in x 2.5 in
Current clamp: 210 mm x 64 mm x 33 mm / 8.2 in x 2.5 in x 1.2 in
Clamp jaw: 86 mm / 3.3 in (exterior)


1 x PCE-PA 8300 3-Phase Power Meter / 3-Phase Power Analyzer
3 x Flexible Rogowski coils (Set 2)
4 x Insulated alligator clips
4 x Safety test lines
6 x 1.5 V AA batteries
1 x 9 V mains adapter
1 x SD memory card
1 x Carrying case
1 x User manual

Write a review

Note: HTML is not translated!
    Bad           Good

PCE-PA 8300-2 Three-Phase Power Analyzer

  • Brand: PCE INSTRUMENTS
  • Product Code: PCE-PA 8300-2 Three-Phase Power Analyzer
  • Availability: Pre-Order
Notice: Undefined index: button_position in /home/u7567509/public_html/system/storage/modification/catalog/view/theme/default/template/product/product.tpl on line 138
  • Rp.0.00

  • Ex Tax: Rp.0.00
Notice: Undefined index: button_position in /home/u7567509/public_html/system/storage/modification/catalog/view/theme/default/template/product/product.tpl on line 322
Notice: Undefined index: button_position in /home/u7567509/public_html/system/storage/modification/catalog/view/theme/default/template/product/product.tpl on line 337

Tags: JUAL PCE-PA 8300-2 Three-Phase Power Analyzer

Whatsapp Chat
Haloo...Belum menemukan alat ukur yang tepat yang Anda cari? Dengan senang hati kami akan membantu.
Technical Support
Informasi Teknis
Sales Support
Informasi Harga
Klik untuk mulai Chat di Whatssapp